Trim Corrections for Jennifer Jones
Sunday, September 24, 2017
Sunday, September 10, 2017
Corrections
NOTE: Siding and bats are not Miratec but are LP brand. The project blog in its entirety can be viewed by going to http://www.reedmountain.com/blog/2017/2/3/stevensville-rural-fire-district-etna-fire-station-1. The following photos are to streamline the review process for warranty of the Miratec trim.
Corrections made were:
1) Removed and replaced all window trim to ensure 1/4" gap around windows. All end cuts were primed with oil-based primer and 2-1/2 mils of exterior latex paint. Gaps were caulked and painted.
2) Cut all vertical trim to allow 1/4" gap over flashing. All end cuts were primed with oil-based primer and 2-1/2 mils of exterior latex paint.
3) Cut vertical and horizontal trim around concrete to allow 1/2" gap. All cuts were primed with oil-based primer and 2-1/2 mils of exterior latex paint.
All other Miratec trim was installed per manufacturer's instructions and no corrections were necessary.
Installation instructions for Milgard windows stated trim to be installed per instructions from trim manufacturer.
BEFORE CORRECTIONS;
CORRECTIONS:
Corrections made were:
1) Removed and replaced all window trim to ensure 1/4" gap around windows. All end cuts were primed with oil-based primer and 2-1/2 mils of exterior latex paint. Gaps were caulked and painted.
2) Cut all vertical trim to allow 1/4" gap over flashing. All end cuts were primed with oil-based primer and 2-1/2 mils of exterior latex paint.
3) Cut vertical and horizontal trim around concrete to allow 1/2" gap. All cuts were primed with oil-based primer and 2-1/2 mils of exterior latex paint.
All other Miratec trim was installed per manufacturer's instructions and no corrections were necessary.
Installation instructions for Milgard windows stated trim to be installed per instructions from trim manufacturer.
BEFORE CORRECTIONS;
| Illustrates window flashing |
| Illustrates window flashing |
| Illustrates window flashing |
| Illustrates window flashing |
| Trim around windows and flashing |
| Illustrates window flashing |
| Illustrates window flashing |
![]() |
| Trim before corrections |
![]() |
| Trim before corrections |
| Trim before corrections |
| Trim before corrections |
CORRECTIONS:
| Window trim removed and horizontal trim cut around windows |
| Trim spaced above flashing |
| Vertical trim cut above concrete |
| Caulking in 1/4" gap and end cuts primed |
| 1/4" gap above trim over flashing |
| 1/4" gap above trim over flashing |
| Trim after corrections |
| Caulking pending paint |
| Caulking pending paint and primed end cut pending paint |
| Caulking pending paint |
| Horizontal trim cut to allow 1/2" gap around concrete and 1/4" gap around flashing. Priming and painting pending. |
| Trim around concrete and windows |
| Cutting of trim around concrete |
| Trim corrected before caulking and paint - end cut primed |
| Trim corrected before caulking and paint - end cut primed |
| Priming end cuts |
| Cut trim above concrete slab |
| Trim with caulking and ends primed |
| Trim with caulking and ends primed |
| Trim with caulking and ends primed |
| Trim with caulking and ends primed |
| Horizontal and vertical trim intersections |
| Window trim caulked pending paint |
| Window trim caulked and painted |
| Window trim caulked pending paint |
| Window trim caulked pending paint |
| Window trim caulked and painted |
| Window trim caulked and painted |
| Window trim caulked pending paint. End cut primed. |
| Window trim caulked and being painted |
| Window trim caulked and being painted |
| Horizontal trim under window caulked and painted |
| Window trim caulked and end cut primed pending paint |
| Window trim caulked pending paint |
| Trim cut per installation instructions |
| Caulked and painted |
| Caulked and painted |
| Caulked and painted |
| Caulked and painted - paint is wet |
| Caulked and painted - paint is wet |
| Caulked and painted |
| Caulked and painted |
| Trim corrected around dormer and window |
| Trim corrected around dormer and window |
| Trim corrected around dormer and window |
| Trim corrected around dormer and window |